Nu-Calgon 4797-0 - Test Kit, Nitrite (K5918-50 W003-0) Each
Nu-Calgon 4797-0 – Nitrite Test Kit (K5918-50 W003-0)
Ensure accurate monitoring of nitrite levels in closed-loop HVAC water systems with the Nu-Calgon 4797-0 Nitrite Test Kit. This professional-grade kit is designed for service technicians maintaining systems treated with nitrite-based corrosion inhibitors, such as Ty-Ion® B20 or Ty-Ion B14A.
Key Features
- Designed for testing nitrite residuals in closed recirculating systems treated with Ty-Ion® corrosion inhibitors.
- Utilizes a ceric ammonium nitrate titration method for high-accuracy readings.
- Each reagent drop equals approximately 40 ppm of nitrite (NaNO₂) concentration.
- Works effectively in systems containing glycol or mixed-metal components.
- Part Number: 4797-0 (Cross-reference: K5918-50 / W003-0).
- Easy-to-use drop-method test for quick field verification of treatment levels.
Benefits
- Corrosion protection – helps maintain correct nitrite residuals to prevent rust and scaling.
- Reduces maintenance costs – prevents damage and downtime caused by under-treated systems.
- Compatible with glycol systems – suitable for both hot and chilled closed loops.
- Fast and reliable – portable design for on-site use without laboratory equipment.
- Trusted quality – engineered by Nu-Calgon for professional HVAC and water treatment applications.
Applications
- Commercial chilled-water systems
- Hydronic heating loops
- Industrial closed-loop cooling circuits
- Data centers, hospitals, office buildings
- Any system treated with nitrite-based corrosion inhibitors
How to Use
- Collect a water sample from the system.
- Add titration reagent drop-by-drop until the color change endpoint is reached.
- Multiply the number of drops by 40 ppm to determine nitrite concentration.
- Compare results to the target residual level (typically around 1000 ppm).
- Adjust treatment levels if required.
Specifications
- Brand: Nu-Calgon
- Model: 4797-0
- Cross Reference: K5918-50 / W003-0
- Test Method: Ceric Ammonium Nitrate Titration
- Range: 0 – 2000 ppm (40 ppm per drop)
- System Compatibility: Water/glycol closed-loop HVAC systems
| Package Quantity | 1 Item |
|---|---|
| Item Returns | Sorry, the item can't be returned |