The White Rodgers 16A60-9 is a manual reset freeze protection control designed to safeguard against freezing conditions in HVAC systems and refrigeration lines. This temperature control is ideal for use in applications where a visual inspection and manual reset are desired after a freeze event.Product Specifications:
- Temperature Range (Open): Opens at 40°F ±5°F
- Manual Reset: Requires manual reset after activation to ensure system inspection
- Capillary Length: 6 feet
- Bulb Size: 3/8" x 5-1/2"
- Switch Action: SPST, opens on temperature rise
- Electrical Ratings:
– 120 VAC: 16.0A resistive, 9.8A full load, 58.8A inrush
– 240 VAC: 8.0A resistive, 4.9A full load, 29.4A inrush - Mounting: Surface-mounted or remote bulb positioning
- Enclosure: NEMA 1